Product image 1

Multifunction Power measuring device

Product ID: 4438 | Type: Power Analyzer

Price:

103.5$

In Stock

Specifications

Classifictaion: Multifunction Power measuring device
Family: UMG
Model: UMG 96L - 255 V
Brand: JANITZA
Origin: Germany
Weight:0.25 KG
Dimensions:96×96×49mm
Category:Power

Fast Shipping

Description:

Janitza UMG 96L (255 V version) is a universal digital power meter designed for continuous measurement and monitoring of electrical parameters in three-phase systems, especially for low-voltage switchgear and distribution panels.

 

Key Features:

  • Voltage Measurement:

    • Direct connection for three-phase systems (with neutral) up to 275 V AC (L-N) and 476 V AC (L-L)1.

    • The standard version is preset for 196–255 V (L-N), with a typical transformer ratio of 400 V (L-L) for low-voltage networks.

  • Current Measurement:

    • Via external current transformers (../5A or ../1A CTs).

  • Measurement Functions:

    • Measures and displays voltage, current, active power (kW), reactive power (kVar), apparent power (kVA), frequency, power factor (cos φ), and energy (kWh, kVarh).

    • Stores minimum and maximum values every 15 minutes; programmable display for all measured values.

  • Display:

    • LCD with backlighting for clear presentation of all measured values.

  • Sampling Rate:

    • 2.5 kHz at 50 Hz, 3.0 kHz at 60 Hz.

  • Power Supply:

    • Powered directly from the measured voltage (L1-N).

  • Mounting:

    • Panel mount (96 × 96 mm), easy installation in switchboards.

  • Operating Temperature:

    • -10°C to +55°C.

  • Protection:

    • Front: IP50 (IP65 with seal), Rear: IP20.

  • Applications:

    • Replacement for multiple analogue instruments (ammeter, voltmeter, power meter, frequency meter, etc.).

    • Energy monitoring, load analysis, and power quality monitoring in low- and medium-voltage distribution boards.

 

Note: The 255 V version is typically used for direct connection in standard low-voltage networks (230/400 V), and the device can also be programmed for use with voltage transformers for higher voltages