Product image 1
Product image 2
Product image 3

Signal Board (AI 1x16 bit RTD)

Product ID: 1139 | Type: 6ES7231-5PA30-0XB0

Price:

151.32$

In Stock

Specifications

Classifictaion: Signal Board (AI 1x16 bit RTD)
Family: S7-1200
Part Number: 6ES7231-5PA30-0XB0
Brand: SIEMENS
Origin: Germany
Product ID1139
Part Number6ES7231-5PA30-0XB0

Fast Shipping

Description:

Siemens 6ES7231-5PA30-0XB0 is a signal board for the SIMATIC S7-1200 programmable logic controller. It provides a single analogue input channel for connecting resistance thermometers (RTDs) such as Pt100, Pt200, Pt500, and Pt1000, as well as measuring resistance and low-voltage signals.

 

Key Features

  • Type: Signal Board SB 1231, Analogue Input (AI 1x16 bit RTD)

  • Analogue Inputs: 1 channel

  • Supported Input Types:

    • Resistance Thermometer: Pt100, Pt200, Pt500, Pt1000

    • Resistance: 0–150 Ω, 0–300 Ω, 0–600 Ω

    • Voltage: ±80 mV (not for thermocouples or current signals)

  • Resolution: 15 bit + sign (overrange)

  • Input Resistance: ≥10 MΩ (for voltage input)

  • Maximum Input Voltage (Destruction Limit): ±35 V

  • Measurement Principle: Integrating

  • Noise Rejection: 85 dB at 10/50/60/400 Hz

  • Common Mode Rejection: >120 dB

  • Power Supply: 24 V DC (current consumption typical 5 mA), 5 V DC from backplane bus (typical 20 mA)

  • Power Loss: Typical 0.5 W

  • Cable Length: Up to 100 m (shielded, twisted pair)

  • Wire Resistance: Max. 20 Ω, 2.7 Ω for 10 Ω RTD

  • Temperature Measurement Units: Adjustable (degrees Celsius or Fahrenheit)

  • Diagnostics:

    • Diagnostic alarm: Yes

    • Diagnostic messages: Wire break, overflow/underflow

    • Diagnostic indication LED: Yes (for status and maintenance)

  • Protection: IP20

  • Operating Temperature: -20°C to +60°C (horizontal), -20°C to +50°C (vertical)

  • Storage Temperature: -40°C to +70°C

  • Relative Humidity: Up to 95% at 25°C (non-condensing)

  • Dimensions: 38 mm (width) × 62 mm (height) × 21 mm (depth)

  • Weight: Approx. 35 g

  • Certifications: CE, CSA, FM, RCM, RoHS, REACH compliant

 

Applications

  • Temperature measurement with Pt100, Pt200, Pt500, or Pt1000 RTDs

  • Resistance measurement (0–150 Ω, 0–300 Ω, 0–600 Ω)

  • Low voltage measurement (±80 mV)

  • Process monitoring and control with SIMATIC S7-1200 PLCs